ACCESSORIES ENCLOSURE
-
AIR CIRCUIT BREAKER (ACB)
-
AUTOMATIC TRANSFER SWITCH
-
BACS, BATTERY & BATTERY CHARGER
-
BUSBAR SYSTEM
-
BUSDUCT & CABLE TRAY
-
CABLE SYSTEM
-
CHANGE OVER SWITCH
-
CURRENT TRANSFORMER & VOLTAGE TRANSFORMER
-
DISCONNECTING SWITCH & LOAD BREAK SWITCH
-
EARTH LEAKAGE CIRCUIT BREAKER (ELCB)
-
EARTHING SWITCHES
-
FUSE
-
HAZARDOUS AREA
-
INSULATION BUSBAR SYSTEM
-
INSULATOR SYSTEM
-
LAMP, PUSH BUTTON & SWITCHES
-
LV DISCONNECTING SWITCH & LOAD BREAK SWITCH
-
MAGNETIC CONTACTOR & OVERLOAD STARTER
-
MCC DRAWER COMPONENTS
-
METERS
-
MINIATURE CIRCUIT BREAKER (MCB)
-
MOLDED CASE CIRCUIT BREAKER (MCCB)
-
OUTDOOR ELECTRICAL COMPONENTS
-
POWER FACTOR CORRECTION
-
PROTECTION RELAYS
-
RESISTOR SYSTEM
-
RETROFIT, RETROFILL & PREVENTIVE MAINTENANCE
-
SCADA & AUTOMATION
-
SOFTSTARTER
-
SURGE ARRESTER
-
TERMINATION SYSTEM
-
TIMER & RELAYS
-
TOOLS & MEASUREMENTS
-
TRANSFORMER
-
UNINTERRUPTIBLE POWER SUPPLY (UPS)
-
VACUUM CIRCUIT BRAKER
-
VACUUM CONTACTOR SWITCH
-
VARIABLE SPEED DRIVE (INVERTER)
BZM Series
BZM Series Eaton’s BZM Series MCCB offers basic protection for electrical designers, panel-builders, contractors and machine builders up to 400A and 50kA.
Simple to operate with high quality features and accessories, the BZM offers most value for installations downstream in the power distribution network. The optional built-in box terminal BT version saves time and eliminates costs for additional parts needed for cable terminations.
Features
• Compact
Unbeatable when it comes to saving space, regardless of whether they are used for energy sub-distribution or as a protection for incoming power in residential or functional buildings.
• Simple
Easy to handle: BZM’s narrow width saves space in the panel. Either a simple connection with cable lugs, or equally simple and convenient - box terminal solution which saves the cost of cable lugs, terminal accessories and wiring time.
• Safe
Reliable quality protects people and assets against short circuits and overload, with the BZM series being designed for the 16 to 400 A range in sub-distribution.
• Standards
Fully compliant with the IEC/EN 60947-2 standards and pollution degree III (IEC/EN 60947).
• Flexibility
BZM offers 5 switching levels from 15kA to 50kA in just 3 frame sizes up to 400A, offering selected 1 / 2 / 3 and 4 pole options, for all typical installation configurations.
• Common Accessories
A wide range of common electrical accessories just snap into position under the front cover, saving valuable mounting and installation time. Standard voltage releases and auxiliary contacts cover all 3 frame sizes, minimizing type varieties, simplifying ordering and reducing multiple stock levels.
Technical details
BZM 1
• Rated current: 16 A up to 125 A
• Breaking Capacity: 15, 18, 25, 36 kA
• Cable fixing: Cable lug M6 or Box Terminal (BZM...-BT)
• Available poles: 1pole, 3pole, 4poles
• Rated Voltage: 400/415V, 50/60Hz
• 3-Position lever: Off - Trip – ON
• Optional rotary handle – Direct or Door Interlocked
• Electrical Supply: Line or Load-Side
• Common voltage trip releases
BZM 2
• Rated current: 125 A up to 250 A
• Breaking Capacity: 25, 36 kA
• Cable fixing: Cable lug M8
• Available poles: 3pole
• Rated Voltage: 400/415V, 50/60Hz
• 3-Position lever: Off - Trip – ON
• Optional rotary handle – Direct or Door Interlocked
• Electrical Supply: Line or Load-Side
• Common voltage trip releases
BZM 3
• Rated current: 250 up to 400A
• Breaking capacity 25, 36 or 50kA/415VAC
• Cable fixing: Cable lug M10 or Tunnel terminal (accessory)
• Rated ltage: 440V, 50/60Hz
• 3-Position lever: Off – Trip – On
• Optional rotary handle – Direct or Door Interlocked
• Electrical Supply: Line or Load-Side
• Common voltage trip releases